VeroLine IP-E (Low Flow, VSD)

VeroLine IP-E (Low Flow, VSD)

New Zealand | Wilo Pumps | VeroLine IP-E (Low Flow, VSD)

Wilo_Logo.png

In-line Design

 

Electronically controlled glanded single pump in in-line design with flange connection and automatic power adjustment

VeroLine IP-E (Low Flow, VSD)



 


Technical Data:

  • Permissible temperature range:
    • -20 °C to +120 °C
  • Mains connection:
    • 3~400 V ±10 %, 50 Hz
    • 3~380 V -5 % +10 %, 60 Hz
  • Protection class IP 55
  • Nominal diameter DN 32 to DN 80
  • Max. operating pressure of standard version: 10 bar (special version: 16 bar)

Advantages

 

  • Energy savings due to integrated electronic power adjustment
  • Optional interfaces for bus communication using plug-in IF-Modules
  • Simple operation with Green Button Technology and display
  • Integrated dual pump management
  • Integrated full motor protection (PTC thermistor sensor) with trip electronics


Construction:

Electronically controlled glanded single pump in in-line design with flange connection and automatic power adjustment.
 


Materials:

  • Pump housing and lantern: (EN-GJL-200)
  • Impeller: PPO-GF30
  • Shaft: 1.4021
  • Mechanical seal: AQEGG; other mechanical seals on request


Application:

Pumping of heating water (acc. to VDI 2035), cold water and water/glycol mixtures without abrasive substances in heating, cold water and cooling systems.

Equipment & Function

 

Operating Modes:

  • Δp-c for constant differential pressure
  • Δp-v for variable differential pressure
  • PID control
  • Constant speed (n=constant)


Manual Functions:

  • Differential pressure setpoint setting
  • Setting the speed (manual control mode)
  • Setting the operating mode
  • Setting the pump ON/OFF
  • Configuration of all operating parameters
  • Fault acknowledgement


Manual Operation Level:

  • Green button and display


External Control Functions:

  • "Overriding Off" control input
  • “External pump cycling” control input (effective only in dual pump operation)
  • Analogue input 0 – 10 V, 0 – 20 mA for constant speed (DDC) and remote setpoint adjustment
  • Analogue input 2 – 10 V, 4 – 20 mA for constant speed (DDC) and remote setpoint adjustment
  • Analogue input 0 – 10 V for actual value signal from pressure sensor
  • Analogue input 2 – 10 V, 0 – 20 mA, 4 – 20 mA for actual value signal from pressure sensor


Signal and Display Functions:

  • Collective fault signal SSM
  • Collective run signal SBM


Data Exchange:

  • Infrared interface for wireless data exchange with IR-Monitor/IR-Stick
  • Plug-in position for Wilo IF-Modules (Modbus, BACnet, CAN, PLR, LON) for connection to building automation


Safety Functions:

  • Full motor protection with integrated trip electronics
  • Access disable


Dual Pump Management (twin-head pump or 2 x single pumps):

  • Main/standby operation (automatic fault-actuated switchover)
  • Pump cycling main/standby operation after 24 hours
  • Parallel operation
  • Parallel operation (efficiency-optimised peak-load activation and deactivation)

 

Model Information
Wilo Pump Range Product Range Overview
Model Information
Wilo Pump Range
Model Information
Wilo Pump Range
Model Information
Wilo Pump Range
Model Information
Wilo Pump Range
Model Information
Wilo Pump Range